October 13, 2024

Logic probe EA112

Usable with: M611

Number of channels 8
Delay < 35ns if 0.25V < |Ui-UT| < 2V
< 40ns if 2V < |Ui-UT| < 5V
< 60ns if 5V < |Ui-UT| < 10V
< 120ns if 10V < |Ui-UT| < 15V
where Ui is voltage before transition and UT is a threshold voltage
Threshold voltage from -5V to +5V with step < 40mV
Accuracy of setting +-100mV +- 2%
Maximum input voltage range +-15V

Required accessories: EA327/8S or EA328